DEADSTOP Overfill Valves for Automatic Diesel & HVO Tank Filling

Complete fuel shut-off for automatic generator tank filling. DEADSTOP is a 2" mechanical overfill prevention valve for diesel and HVO day tanks, belly tanks and aboveground storage tanks. Its float-operated, zero-leak closure provides additional protection during unattended fuel transfer from bulk storage.

Choose fixed or adjustable float versions, with female BSPT inlet adaptors and tank mounting accessories available. Explore the features and selection guide.

Related Products

Overfill protection for automatic day-tank filling

Generator fuel systems often transfer diesel or HVO automatically from a bulk storage tank to a day tank or generator belly tank. These filling cycles can take place unattended, making the receiving tank’s overfill protection an important equipment-selection decision.

DEADSTOP provides a mechanical layer of protection alongside the system’s normal filling controls and alarms. When fuel reaches the float’s activation level, the valve closes completely to stop incoming flow. No electrical supply or external control signal is required to actuate the valve.

For generator fuel-system installers, tank manufacturers and critical-power specifiers, it offers a float-operated shut-off option for pressure-fed tank-filling duties.

Why complete shut-off matters

Some overfill valves intended for supervised road-tanker deliveries incorporate a deliberate leak path. After activation, the driver stops delivery at the tanker, then drains residual fuel from the delivery hose and connecting pipework through the valve into the tank.

That drain-down function serves a different purpose from complete shut-off. In an unattended bulk-to-day-tank transfer system, a deliberate leak path can allow fuel to continue entering the receiving tank while upstream pressure remains.

DEADSTOP stops the flow completely. Its zero-leak closure has no deliberate drain-down path through the actuated valve, making this a key distinction when selecting overfill protection for automatic filling.

Features that support reliable fuel shut-off

  • Direct float operation: responds to the fuel level in the receiving tank, providing mechanical overfill protection should the normal filling controls fail to stop delivery.
  • Zero-leak closure: completely stops incoming fuel when the float actuates the valve.
  • Pressure-assisted sealing: the valve shuts in the direction of flow, with fill pressure helping maintain the closed seal.
  • 10–500 litres per minute: accommodates a range of pressure-fed filling duties, including low-flow transfer applications.
  • Maximum operating pressure of 10 bar: provides a defined pressure limit against which to check the transfer-system duty.
  • Cartridge construction: allows installation and access for examination through a single 2" tank opening, subject to the specified mounting arrangement.
  • Factory tested: every valve is tested before leaving the manufacturer.

Choose your float arrangement

Select the float version to suit the valve mounting position and the tank’s required maximum fuel level.

Fixed float — DEAD-STOP

The standard float closes the valve when fuel reaches approximately 145 mm below the bottom of the valve. Choose this version where the standard activation position provides the required shut-off level.

Adjustable float — DEAD-STOP-AF

A cut-to-length float extension allows a lower activation position to suit the tank arrangement. This provides flexibility where additional ullage or a lower maximum fuel level is required.

Both listed valve versions include a 2" BSP locknut. Check available float clearance and follow the manufacturer’s instructions when determining the adjustable tube length. Measurements below the valve are not automatically measurements below tank brimfull.

Connect threaded inlet pipework

DEADSTOP has a 2" square-flange inlet. Female BSPT adaptor kits connect this inlet to threaded pipework in the following sizes.

Threaded inlet adaptor selection
Female connection Adaptor stock code
1" BSPT RIS-FLANGE10F
1½" BSPT RIS-FLANGE15F
2" BSPT RIS-FLANGE20F

Select the inlet adaptor separately from the tank mounting components. Check the tank opening, mounting dimensions and pipework arrangement against the manufacturer’s installation instructions.

Integrating DEADSTOP into a generator fuel system

Complete valve closure causes pressure to rise in the upstream pipework. The transfer pump, shutdown controls and pressure-protection arrangement must accommodate a closed delivery path within the equipment’s operating limits.

The valve reopens only after upstream pressure has dissipated and the fuel level has fallen. Account for this behaviour when specifying the transfer controls and restart sequence.

Install the valve upright, provide clearance for unrestricted float movement and support connecting pipework to avoid stressing the valve. Follow the manufacturer’s installation and maintenance instructions, and test correct operation before putting the system into service.

Get help selecting your valve and accessories

PFS Fueltec supports generator fuel-system installers, tank builders and specifiers with equipment supply and practical product-selection guidance. We can help identify the DEADSTOP float arrangement, inlet adaptor and mounting accessories for your requirement.

Send us your tank drawing, required shut-off level, fuel type, transfer flow, delivery pressure and pipework size.

Email our fuel equipment team or call 01376 535260.